Outback Power 8kW Isolated String Inverter - PRO480-8K |
Outback, 8kW 480VAC 3-Phase Isolated String Inverter, PRO480-8K |
Features
|
General Information | |
Manufacturer: | Outback Power |
Product Line: |
PRO Series |
Model ID: |
PRO480-8K |
Certifications and Safety Ratings: | ![]() |
Mechanical Data |
|
Technology: | Isolated String Inverter |
Dimensions: |
18.75 x 13.13 x 3.00 inches |
Weight: | 24.00 lbs |
Efficiency: |
Peak: 98.6%, CEC: 98% |
Operating Temperature Range: | -40°F to +150°F |
Power Consumption: | Standby: <4.5W, Night: <4.5W |
Cooling: | Natural Convection, No Fan |
Communication: | Power-Line |
Environmental Rating: | Outdoor/Rooftop, NEMA 6, IP67 |
Certifications: | Listed to UL1741, IEEE 1547 (Utility Interactive), CSA C22.2 No. 107.1, FCC Part 15, Meets the Requirements of NEC 690.11 |
Electrical Data |
|
Maximum Open Circuit Voltage: | 1000VDC (Per String) |
Full Power MPPT Range: |
425 to 850VDC (Per String) |
PV Start Voltage: | 200VDC |
DC Allowable Stacking Ratio: |
Must Not Exceed 6.375 Under Any Circumstances |
DC Maximum Input: | Current (per DC Input): 10A; Short Circuit Current: 30A; Source Back Feed Current to Input Source: 0A |
DC Disconnect Means: | DC Connector Has Been Evaluated and Approved for Use As the Load-Break Disconnect Required by the NEC (NEC Section 690.17, Allowed by the Exception of Meeting Requirements Specified in 690.33). |
AC Maximum: | Continuous Total Output Power (to 45°C): 8kW; Continuous Output Current (per Phase): 9.6A; Output Current Protection: 60A |
AC Derate (40-65°C): | -150W per °C |
AC Nominal Output Current: | 9.6A (per Phase) |
AC Three-Phase System Compatibility: | 480V Wye, Three Phases, Neutral, and Ground |
AC Voltage Range (Phase to Phase): | Minimum: 422V; Nominal: 480V; Maximum: 528V |
AC Voltage Range (Phase to Neutral): | Minimum: 244V; Nominal: 277V; Maximum: 305V |
AC Output Frequency Range: | Minimum: 59.3Hz; Nominal: 60Hz; Maximum: 60.5Hz |
Power Factor: | >0.98 |
AC Lower Trip Limit (Frequency): | Default: (±1Hz):59.3Hz; Adjustment (±1Hz):57 to 59.3Hz; Clearing Time Default: (±2 Cycles):0.16s; Clearing Time Adjustment: (±2 Cycles):0.16 to 300s |
AC Lower Trip Limit (Voltage Phase to Neutral): | Default: (±2%):245V; Adjustment: (±2%):220 to 245V; Clearing Time Default: (±2 Cycles):2s; Clearing Time Adjustment: (±2 Cycles): 1 to 20s |
AC Upper Trip Limit (Frequency): | Default: (±1Hz):60.5Hz; Adjustment: (±1Hz):60.5 to 62.0Hz; Clearing Time Default: (±2 Cycles):0.16s; Clearing Time Adjustment: (±2 Cycles):0.16 TO 300s |
AC Upper Trip Limit (Voltage Phase to Neutral): | Default: (±2%):305V; Adjustment: (±2%):305 to 315V; Clearing Time Default: (±2 Cycles):1s; Clearing Time Adjustment: (±2 Cycles):1 to 20s |
AC Reconnect Delay: | Default: 5min; Adjustment: 1s to 10min |
AC Synchronized In-Rush Current: | 0A |
Maximum Output Fault Current and Duration: | 10A, <0.5ms |
AC Minimum Wire Gauge: | 14 AWG |
AC Disconnect Means: | The AC Connector Has Been Evaluated and Approved for Use as the Load-Break Disconnect Required by the NEC (NEC Section 690.17, Allowed by the Exception of Meeting Requirements Specified in 690.33). |
Datasheets |
|
Document | Type |
![]() |
Specifications |
![]() |
Installation Guide |
![]() |
Quick Start Guide |
Warranty | 10 Year Standard Warranty |
![]() |
Warranty |
Terms & Conditions |
|
Shipping: | Shipping Policy |
Returns: | Returns Policy |
Payments: | We accept: Visa, MasterCard, Discover, and American Express. We also accept checks, direct deposit and wire transfers for large orders. |
Warranty: 10 Year Standard Warranty